MLS300-S Rotary Series Limit Switch(Stainless Steel)
MLS Series Limit Switch is consistent with IP Protection standard, ISO5211 standard and Namur standard. The shell mainly include impact type, standard type, explosion proof type and stainless steel type; Mechanical switch, proximity switch are selectable for switch specification, which provide users with safety, high-quality and reliable automatic products.
MLS300-S series limit switch is used for indicating switch position locally and output of switch signal remotely of automatic valve. The shell material is SS316L. Designed with explosion-proof structure, suitable for ExdIICT6 standard, the products are widely used in petroleum, natural gas and other industries.
Characteristics
Seal design for double shafts, each shaft is connected with the upper cover and base respectively, easy to disassemble ad install, and has good protection function. |
Accurate concentric design to ensure accurate valve position. |
With two dimensional indicators, which can indicate the valve position with full angle. |
In line with Namur standard to realize the max.interchangeablity. |
With anti-off bolt in the upper cover to prevent falling off when disassembled. |
The shell material is SS316L and can be used for highly corrosive environment. |
With double wire interface, double G3/4’’ pipe interface, other standards are selectable. |
Multiple contact terminal row, terminal blocks with 8 standard contacts. Multiple terminals are optional. |
The spring loaded can be debugged without extra tools. |
Technical Parameters
ITEM / MODEL |
MLS300 |
MLS300-S |
|
Body Material |
Aluminum |
SS316L |
|
Paintcoat |
Polyester powder coating |
- |
|
Cable Entry |
2-NPT3/4” |
2-NPT3/4” |
|
Terminal Blocks |
6 points |
8 points |
|
Enclosure Grade |
IP67 |
||
Explosion Proof |
ExdIICT6 |
||
Stroke |
90° |
||
Ambient Temp. |
-20 to 70℃ |
||
Switches |
SPDT*2 / Proximity Switch*2 |
||
Switch Specification |
Mechanical Switch |
16A 125VAC / 250VAC, |
|
0.6A 125VDC |
|||
10A 30VDC |
|||
Proximity Switch |
Intrinsically safe: 8VDC, NC |
||
None explosion: 10 to 30VDC, ≤150mA |
|||
Position Transmitter |
4 to 20mA, with 24VDC Supply |